Why is the LED display frequently tripping? Here's a simple analysis of frequent LED trips. Hope to solve your LED display trip problem.
Leakage protector layout is not reasonable
Due to the special features of the LED display installation site, such as incorrect wiring, broken lines, damage to the leakage protector inside the switch box, and some electrical appliances that do not pass through the switch box, as well as the inevitable malfunction and rejection of the leakage protector itself. In addition, the leakage protection device was not arranged according to the actual electricity situation, resulting in frequent tripping of the total leakage protection device.
In addition to strengthening management, it is also necessary to rationally arrange the leakage protector according to the actual situation from the technical point of view. The leakage protection device on the main power supply of the incoming line can be mainly used as a total protection against electrical fire hazards and electrical short-circuits. It also serves as backup protection for each small leakage protection range. Its rated leakage action current can be between 200 and 500 mA. Interval selection, rated leakage action time can choose 0.2 ~ 0.3s. In this way, the influence of surge voltage, surge current, and electromagnetic interference on the total leakage protector can be greatly reduced, and the selectivity and reliability of the total leakage protector action can be improved. If the secondary leakage protection within each leakage protection range can be effectively protected, the frequent tripping probability of the total leakage protector on the construction site can be greatly reduced.
There is no effective secondary or tertiary leakage protection within the scope of protection
The last-stage leakage protector in the switch box is the main protection of the power equipment. If the last-stage leakage protector is not installed, damaged or improperly selected, it may cause frequent tripping of the upper leakage protector. Because there are many metal conductors in the LED display, there are many wire joints. If the wire insulation is not very good, it will lead to frequent leakage; some also add some sockets, in many cases do not install the leakage protection device, often causing leakage . Only by forming an effective secondary or tertiary leakage protection mode within each protection range can the frequent tripping of the leakage protector be effectively reduced.
Leakage protectors have their own limitations
(1) Current leakage protectors, whether of electromagnetic type or electronic type, use magnetic induction voltage transformers to pick up leakage currents in the main circuit of the electrical equipment. Three-phase or three-phase four-wires cannot be completely balanced in the magnetic ring. The three-phase power load of the LED display cannot be completely balanced. Under high current or high overvoltage, a certain electromotive force is induced in the magnetic ring with high magnetic permeability. This electromotive force is large enough to a certain extent. , it will cause the leakage protector to trip. Because the larger rated current leakage protector uses a relatively large magnetic ring, the generated leakage magnetic flux is also relatively large, and the leakage current must overcome the magnetizing force of the magnetic ring itself, resulting in a larger rated current of the actually used leakage protector. The lower the sensitivity, the greater the rejection rate.
(2) The leakage protector has a zone of undefined operation between the rated leakage action current and the rated leakage action current. When the leakage current of the leakage protector fluctuates in this area, the leakage protector may trip irregularly.
Leakage protector selection is unreasonable
(1) The rated leakage current used in the switch box exceeds 30 mA or is more than twice the rated current of the equipment, or a time-delay type leakage protector is used because of the rated leakage current. Improve or protect the decline of the sensitivity, leakage leakage occurs, the last stage leakage protector does not operate, the upper leakage protector may act
(2) The starting current when the LED display is powered on is often relatively large. This large current may trip the leakage protector. Therefore, the display box should be powered up in batches as much as possible. In addition, electromagnetic leakage protectors that are less sensitive to surge overvoltages and overcurrents should generally be selected; or electronic leakage protectors that are 1.5 to 2 times larger than the rated current should be selected, but as the last stage leakage protection, rated leakage action The current should not exceed 30mA.
In short, the frequent tripping of the leakage protector is the result of a combination of various factors. The most important thing is to rationally arrange the leakage protector, reduce the protection range of the second or third class leakage protector, and correctly select the leakage protector and the wiring so that each The second or third-order leakage protectors in the scope are in effective protection status; on the other hand, it is to strengthen the management of electricity use and improve the quality of the electricity users through training, and eliminate the non-electrical wiring, so that the safety of the electricity can be improved. It can also reduce the frequent tripping of the leakage protector and create better power supply conditions for the normal operation of the LED display.
Yogurt Production Line
1. Yogurt Production Line is combined with Milk Storage Tank, Milk Preheating Tank, Milk Homogenizer, Milk Pasteurizing Tank, Milk Fermentation Tank, Yogurt Filling Machine which can fill yogurt into glass or plastic bottles.
2. We have farm use capacity, 200L/300L/500L per batch. You want more, we also can customize it according to customer's needs.
3. We also can make the liquid yogurt and set yogurt, just need to match different machine to finish it.
We also mainly manufacture: meat processing machines, milk processing machines, egg processing machines, fruit vegetable machines etc. We have years of exporting experiences, sincerely hope for copperation!