Regarding if chiller CW-5000 alarm is sounding but no error code is being displayed and can not turn the alarm off

In alarming state, the alarm sound could be suspended by pressing any button, but the alarm display remains until the alarm condition is eliminated. Besides, if there is no error code and the red light on, that maybe water flow alarm. Troubleshooting as below: When the red light on and the controller display water temp in normal, you can connect the water inlet with outlet by a hose, if the alarm is eliminated, that means the internal water circulating loop work in normal and the outside pipe blocked; If the chiller continue to alarm, that means internal water loop blocked. When the red light on, the temperature no display or show 8.88, firstly we should cutt off the power line of water pump and check if the temperature controller display water temp in normal, we can judge the water pump failure, pls change it; Howerever if the temperature controller can`t display water temp or show 8.88, we can judge the power of water pump failure, and we should change another one. Feel free to contact us. More about S&A chiller: http://?

chiller

CONTACT S&A

TEL:+86-20-89301885,

FAX:+86-20-84309967

SKYPE: teyuchiller

Email:

Website: http://

Tealight Candles


Tea light candle,is the kind of colored candles, also known as candle for coffee & tea.Its small size, long burning time, is the essentials of western family.Apply to hotels, churches, religious activity places. it is with aluminum cans casting wax, commonly used for birthday, burning time from 1-3 hours according to calculate weight, generally used in bars, KTV, cafe ,and the candle light like tea light,the candle light same as the tea light,so called the tea light candle


Tealight Candles,Colorful Tealight Candle,Paraffin Wax Tealight Candles,Colored Candles,Candle Light

HEBEI GEMMY IMP.& EXP.CO.,LTD , https://www.hbgemmy.com